Float voltage: EnerSys temperature compensation
Float voltage per cell against battery temperature: the EnerSys OPzV table (2.37 V at −10 °C … 2.25 V at 20 °C … 2.21 V at 40 °C) with the ±30 mV/cell alert band. Dot: measured string voltage ÷ 54 at the measured battery temperature (grey while the charger is off). Below: float current, measured vs. the twin's expectation.
Ohmic value per cell vs. baseline
Internal resistance of each of the 54 cells from the battery monitoring system, against the EnerSys 0.51 mΩ at 20 °C corrected to the battery temperature. Lines: +20 % investigate, +50 % act (typical field practice). Red bar: a cell more than 1.5× the string mean.
DC system
AC supply, thyristor charger with its filter, the 110 V DC bus and its loads, the 54-cell battery and the insulation monitor, with live sensor values. Red = beyond the twin's alarm limit.
Condition sensors
Bars against the alarm limits in the twin file (red line).